Data center energy Live model

You are the facility engineer of a 1 MW data hall: chillers, a chilled-water loop, UPS batteries and a standby generator. Heat flows from servers to air to water to the outdoors — and every watt you spend on cooling shows up in the PUE.

What you will learn

Simulator

Time 0 min
Server inlet temperature 22.4 °C · Chillers running 2/3 · Chillers tripped (latched) 0 · UPS battery 100% · 25 °C22.4 °C · IT 803 kW#1#2#3UPS 100%⚡ grid · 🔌🌡 25 °C · COP 5.1 · PUE 1.34
  • Inlet < 24 °C
  • Inlet ≥ 27 °C
  • Inlet ≥ 32 °C
  • Chiller running
  • Chiller starting (5 min)
  • Chiller tripped (latched until reset)

Controls

Chiller #1…#n. A newly started chiller needs 5 min before it cools.

Warmer water = better chiller efficiency, but warmer server inlets.

Batch jobs postponed to later: less heat and power now.

Uses cold outdoor air through a dry cooler when it is cold enough.

Evaporates water to cool condenser air: better efficiency, water use.

Only needed if the automatic start fails. Takes 3 min.

Clears a chiller safety trip once the fault has been checked; accepted from 15 min after the trip.

Indicators

Server inlet temperature
22.4°C
normal
PUE
1.34
normal
Facility power
1076kW
UPS battery
100%
normal
Chilled-water temperature14.0 °C
Chiller COP5.1
IT load803 kW
Chillers running2
Chillers available (not tripped)3
Chillers tripped (latched)0
Trip reset possible in0 min
WUE0.00 L/kWh
CO₂ emissions484 kg/h

Trend

Server inlet temperature: — °C40.015.0

Crisis scenarios

Level 1 · Chiller trip at peak

A hot afternoon, 32 °C outside. IT draws 850 kW on two of three chillers, and the chilled water runs at 16 °C to save energy — which leaves the server inlets only about 2 K below the ASHRAE recommended limit. One chiller is about to trip. Keep the inlets inside the recommended range, keep the IT work running, and get the plant back to full redundancy.

  • Inlet never above 27 °C
  • Inlet ≤ 25 °C at the end (back to normal)
  • Average IT load ≥ 750 kW (do not just switch servers off)
  • All three chillers available again at the end (tripped unit reset)

Level 2 · Heatwave and a demand-response call

Outdoor temperature climbs from 30 °C to 42 °C. Chillers lose capacity and efficiency. Then the grid operator issues a demand-response request: keep this site’s facility power under 900 kW for half an hour.

  • Inlet never above 27 °C
  • Average facility power ≤ 900 kW during the request
  • Average IT load ≥ 720 kW over the scenario

Level 3 · Grid outage, generator fails to start

The grid drops. The generator should pick up within ten seconds — this time it does not. Servers are on UPS batteries with roughly ten minutes of energy, and the chillers are dark.

  • No IT outage
  • Battery never below 72 %
  • Inlet never above 25 °C

Basis — the model behind the numbers

Every relation the simulator uses, with its source. Constants marked as assumptions are illustrative calibrations.

Air node energy balance: servers heat the air, cooling coils move heat into the chilled water.
C_air · dT_air/dt = P_IT + P_fans − Q_CRAH, Q_CRAH = UA · (T_air − T_chw)[4][11]Assumption: capacitances, coil conductance, chiller size and battery energy are illustrative values for a 1 MW hall.
Water node energy balance: the loop’s thermal mass buffers the gap between heat load and chiller capacity.
C_w · dT_chw/dt = Q_CRAH − Q_chillers − Q_econ, C_w = 20 m³ × 4186 J/(kg·K)[4]
Chiller efficiency as a fixed fraction of the Carnot limit — it falls as outdoor air gets hotter. The evaporator temperature follows the actual chilled-water loop temperature (2 K below it), not the setpoint, so a loop that warms after a trip briefly raises the COP.
COP = 0.45 · T_evap / (T_cond − T_evap), T_evap = T_chw − 2 K, T_cond = T_air,out + 12 K [K][5]Assumption: capacitances, coil conductance, chiller size and battery energy are illustrative values for a 1 MW hall.
Power usage effectiveness: total facility power over IT power (1.0 is the ideal).
PUE = P_facility / P_IT[1][12][8]
Water usage effectiveness; evaporated water from the energy needed to cool the condenser air.
WUE = water (L) / IT energy (kWh); evaporation = m_air · c_p · ΔT / h_fg[2][7]
ASHRAE thermal envelope for server inlet air.
recommended 18–27 °C · A1 allowable 15–32 °C[3]
UPS battery energy drains with the protected load until the generator takes over.
E_batt(t+Δt) = E_batt − (P_IT + P_fans + P_pumps)/η_UPS · Δt (energy balance); generator ≤ 10 s[6]Assumption: capacitances, coil conductance, chiller size and battery energy are illustrative values for a 1 MW hall.
After any power transfer the chillers stop and must restart.
chiller restart after any power transfer = 5 min (quick-start; typical 10–15 min)[11]
Emissions from grid electricity intensity, or from diesel when the generator runs.
CO₂ = P_facility × grid intensity (≈450–650 g/kWh in the scenarios); diesel ≈ 2.69 kg CO₂/L[9][10][13]
Other operating constants used by the model.
chillers 3 × 450 kW, derate 2.5 %/K above 35 °C · adiabatic effectiveness 70 % · loop P-gain 150 kW/K · IT shutdown at 40 °C inlet · manual generator start 3 min · chiller trip reset accepted 15 min after the trip · battery 150 kWh (≈10 min at full load), recharge 10 %/h · UPS η 95 %Assumption: capacitances, coil conductance, chiller size and battery energy are illustrative values for a 1 MW hall.

Randomness: a seeded mulberry32 generator; distributions used — uniform, exponential (inverse CDF), normal (Box–Muller), Poisson (Knuth). The seed is shown and shareable.

Sources

  1. ISO/IEC 30134-2:2016 Data centres — Key performance indicators — Part 2: Power usage effectiveness (PUE) — ISO/IEC, 2016
  2. ISO/IEC 30134-9:2022 Data centres key performance indicators — Part 9: Water usage effectiveness (WUE) — ISO/IEC, 2022
  3. ASHRAE TC 9.9 — Thermal Guidelines for Data Processing Environments (recommended inlet 18–27 °C; class A1 allowable 15–32 °C) — ASHRAE, 2021
  4. F. P. Incropera et al. — Fundamentals of Heat and Mass Transfer: lumped capacitance, Q = UA·ΔT — Wiley, 2011
  5. Y. A. Çengel, M. A. Boles — Thermodynamics: An Engineering Approach — Carnot COP of refrigerators, COP = T_L/(T_H − T_L) — McGraw-Hill, 2019
  6. NFPA 110 — Standard for Emergency and Standby Power Systems (Type 10: power restored within 10 s) — NFPA
  7. IAPWS — enthalpy of vaporization of water (≈2442 kJ/kg at 25 °C, 2257 kJ/kg at 100 °C) — IAPWS / NIST Chemistry WebBook
  8. Directive (EU) 2023/1791 (Energy Efficiency Directive) Art. 12 and Commission Delegated Regulation (EU) 2024/1364 — data-centre reporting — EUR-Lex, 2023–2024
  9. Ember — Global Electricity Review 2025: world average grid carbon intensity 473 gCO₂/kWh (2024) — Ember, 2025
  10. IPCC AR5 WG3 Annex III — life-cycle emissions of electricity supply technologies (median gCO₂eq/kWh) — IPCC, 2014
  11. Schneider Electric (APC) White Paper 179 — Data Center Temperature Rise During a Cooling System Outage — Schneider Electric
  12. Uptime Institute Global Data Center Survey 2025 — average annual PUE 1.54 — Uptime Institute, 2025
  13. U.S. EPA — Greenhouse Gas Emissions from a Typical Passenger Vehicle: 10,180 g CO₂ per gallon of diesel (≈2.69 kg/L) — U.S. EPA

Who does this for a living

Educational model — not for operational decisions. Real sites calibrate every constant to their own equipment and data.