Makamashin cibiyar bayanai Samfurin kai-tsaye

Kai ne injiniyan wurin zauren bayanai na 1 MW: chillers, madaurin ruwan sanyi, batirin UPS da janareta na jiran-aiki. Zafi yana tafiya daga sabar zuwa iska, daga iska zuwa ruwa, sannan zuwa waje — kuma kowane watt da ka kashe a sanyaya yana bayyana a PUE.

Abin da za ka koya

Na'urar koyi

Lokaci 0 min
Zafin mashigar sabar 22.4 °C · Chillers masu aiki 2/3 · Chillers da suka yanke (a kulle) 0 · Baturin UPS 100% · 25 °C22.4 °C · IT 803 kW#1#2#3UPS 100%⚡ grid · 🔌🌡 25 °C · COP 5.1 · PUE 1.34
  • Mashiga < 24 °C
  • Mashiga ≥ 27 °C
  • Mashiga ≥ 32 °C
  • Chiller yana aiki
  • Chiller yana tashi (5 min)
  • Chiller ya yanke (a kulle har sai an sake saitawa)

Sarrafawa

Chiller #1…#n. Sabon chiller da aka kunna yana buƙatar minti 5 kafin ya fara sanyaya.

Ruwa mai ɗumi = ingancin chiller mai kyau, amma mashigar sabar ta yi ɗumi.

Ayyukan rukuni da aka jinkirta zuwa gaba: ƙarancin zafi da wuta a yanzu.

Yana amfani da iskar waje mai sanyi ta cikin na'urar sanyaya busasshiya idan ta isa sanyi.

Yana ƙafar da ruwa domin sanyaya iskar na'urar condenser: ingantaccen aiki, amma yana ɓata ruwa.

Sai idan kunnawa ta atomatik ta gaza. Yana ɗaukar minti 3.

Yana share yankewar tsaro na chiller bayan an duba matsalar; ana karɓa daga minti 15 bayan yankewar.

Alamomi

Zafin mashigar sabar
22.4°C
daidai
PUE
1.34
daidai
Wutar wurin
1076kW
Baturin UPS
100%
daidai
Zafin ruwan sanyi14.0 °C
COP na chiller5.1
Nauyin IT803 kW
Chillers masu aiki2
Chillers da ake da su (ba su yanke ba)3
Chillers da suka yanke (a kulle)0
Za a iya sake saita yankewa nan da0 min
WUE0.00 L/kWh
Hayaƙin CO₂484 kg/h

Yanayi

Zafin mashigar sabar: — °C40.015.0

Yanayin rikici

Mataki 1 · Chiller ya fita daga aiki a lokacin kololuwa

Rana mai zafi da yamma, 32 °C a waje. IT yana jan 850 kW kan chillers biyu cikin uku, kuma ruwan sanyi yana gudana a 16 °C don ajiye makamashi — wanda ke bar mashigar sabar kusan 2 K kacal ƙasa da iyakar da ASHRAE ta ba da shawara. Chiller ɗaya zai yanke ba da daɗewa ba. Ka riƙe mashigai a cikin kewayen da aka ba da shawara, ka ci gaba da aikin IT, kuma ka mayar da tsarin zuwa cikakken ajiya (redundancy).

  • Mashiga ba ya wuce 27 °C
  • Mashiga ≤ 25 °C a ƙarshe (komawa daidai)
  • Matsakaicin nauyin IT ≥ 750 kW (kada ka kashe sabar kawai)
  • Dukkan chillers uku sun sake samuwa a ƙarshe (an sake saita wanda ya yanke)

Mataki 2 · Raƙuman zafi da kiran rage amfani da wuta

Zafin waje yana tashi daga 30 °C zuwa 42 °C. Chillers suna rasa ƙarfi da inganci. Sai mai sarrafa grid ya aiko da buƙatar rage amfani da wuta: ka riƙe wutar wannan wuri ƙasa da 900 kW na rabin sa'a.

  • Mashiga ba ya wuce 27 °C
  • Matsakaicin wutar wuri ≤ 900 kW a lokacin buƙatar
  • Matsakaicin nauyin IT ≥ 720 kW a duk yanayin

Mataki 3 · Grid ya ɗauke, janareta ya gaza kunnuwa

Grid ya ɗauke. Ya kamata janareta ya karɓa cikin daƙiƙa goma — a wannan karon bai yi ba. Sabar suna kan batirin UPS tare da makamashi na kusan mintuna goma, kuma chillers a kashe suke.

  • Babu katsewar IT
  • Baturi ba ya faɗi ƙasa da 72 %
  • Mashiga ba ya wuce 25 °C

Tushe — samfurin da ke bayan lambobin

Kowace alaƙa da na'urar koyi ke amfani da ita, tare da tushenta. Ƙayyadaddun ƙimomin da aka yi wa alama a matsayin zato daidaitawa ne na misali.

Daidaiton makamashin wurin iska: sabar suna ɗumama iska, ɗigiyoyin sanyaya suna matsar da zafi zuwa ruwan sanyi.
C_air · dT_air/dt = P_IT + P_fans − Q_CRAH, Q_CRAH = UA · (T_air − T_chw)[4][11]Zato: ƙarfin riƙe zafi, jagorancin ɗigiya, girman chiller da makamashin baturi ƙimomi ne na misali don zauren 1 MW.
Daidaiton makamashin wurin ruwa: nauyin zafin madauki yana rage gibin da ke tsakanin nauyin zafi da ƙarfin chiller.
C_w · dT_chw/dt = Q_CRAH − Q_chillers − Q_econ, C_w = 20 m³ × 4186 J/(kg·K)[4]
Ingancin chiller a matsayin ɓangare tabbatacce na iyakar Carnot — yana raguwa yayin da iskar waje ke ƙara zafi. Zafin evaporator yana bin ainihin zafin madaurin ruwan sanyi (2 K ƙasa da shi), ba maƙasudi ba, don haka madaurin da ke ɗumama bayan yankewa yana ɗaga COP na ɗan lokaci.
COP = 0.45 · T_evap / (T_cond − T_evap), T_evap = T_chw − 2 K, T_cond = T_air,out + 12 K [K][5]Zato: ƙarfin riƙe zafi, jagorancin ɗigiya, girman chiller da makamashin baturi ƙimomi ne na misali don zauren 1 MW.
Power usage effectiveness: jimillar wutar wurin ÷ wutar IT (1.0 shi ne mafi kyau).
PUE = P_facility / P_IT[1][12][8]
Water usage effectiveness; ruwan da ya ƙafe daga makamashin da ake buƙata don sanyaya iskar condenser.
WUE = water (L) / IT energy (kWh); evaporation = m_air · c_p · ΔT / h_fg[2][7]
Iyakar zafi ta ASHRAE don iskar da ke shiga sabar.
recommended 18–27 °C · A1 allowable 15–32 °C[3]
Makamashin baturin UPS yana ƙarewa tare da kayan da ake karewa har sai janareta ya karɓa.
E_batt(t+Δt) = E_batt − (P_IT + P_fans + P_pumps)/η_UPS · Δt (energy balance); generator ≤ 10 s[6]Zato: ƙarfin riƙe zafi, jagorancin ɗigiya, girman chiller da makamashin baturi ƙimomi ne na misali don zauren 1 MW.
Bayan kowane canjin wuta, chillers suna tsayawa kuma dole ne a sake kunna su.
chiller restart after any power transfer = 5 min (quick-start; typical 10–15 min)[11]
Hayaƙi daga ƙarfin carbon na wutar lantarkin grid, ko daga dizal lokacin da janareta ke aiki.
CO₂ = P_facility × grid intensity (≈450–650 g/kWh in the scenarios); diesel ≈ 2.69 kg CO₂/L[9][10][13]
Sauran ƙayyadaddun ƙimomin aiki da samfurin ke amfani da su.
chillers 3 × 450 kW, derate 2.5 %/K above 35 °C · adiabatic effectiveness 70 % · loop P-gain 150 kW/K · IT shutdown at 40 °C inlet · manual generator start 3 min · chiller trip reset accepted 15 min after the trip · battery 150 kWh (≈10 min at full load), recharge 10 %/h · UPS η 95 %Zato: ƙarfin riƙe zafi, jagorancin ɗigiya, girman chiller da makamashin baturi ƙimomi ne na misali don zauren 1 MW.

Rashin tsari: mai samar da mulberry32 mai iri; rarrabawar da aka yi amfani da su — uniform, exponential (inverse CDF), normal (Box–Muller), Poisson (Knuth). Ana nuna iri kuma ana iya raba shi.

Tushe

  1. ISO/IEC 30134-2:2016 Data centres — Key performance indicators — Part 2: Power usage effectiveness (PUE) — ISO/IEC, 2016
  2. ISO/IEC 30134-9:2022 Data centres key performance indicators — Part 9: Water usage effectiveness (WUE) — ISO/IEC, 2022
  3. ASHRAE TC 9.9 — Thermal Guidelines for Data Processing Environments (recommended inlet 18–27 °C; class A1 allowable 15–32 °C) — ASHRAE, 2021
  4. F. P. Incropera et al. — Fundamentals of Heat and Mass Transfer: lumped capacitance, Q = UA·ΔT — Wiley, 2011
  5. Y. A. Çengel, M. A. Boles — Thermodynamics: An Engineering Approach — Carnot COP of refrigerators, COP = T_L/(T_H − T_L) — McGraw-Hill, 2019
  6. NFPA 110 — Standard for Emergency and Standby Power Systems (Type 10: power restored within 10 s) — NFPA
  7. IAPWS — enthalpy of vaporization of water (≈2442 kJ/kg at 25 °C, 2257 kJ/kg at 100 °C) — IAPWS / NIST Chemistry WebBook
  8. Directive (EU) 2023/1791 (Energy Efficiency Directive) Art. 12 and Commission Delegated Regulation (EU) 2024/1364 — data-centre reporting — EUR-Lex, 2023–2024
  9. Ember — Global Electricity Review 2025: world average grid carbon intensity 473 gCO₂/kWh (2024) — Ember, 2025
  10. IPCC AR5 WG3 Annex III — life-cycle emissions of electricity supply technologies (median gCO₂eq/kWh) — IPCC, 2014
  11. Schneider Electric (APC) White Paper 179 — Data Center Temperature Rise During a Cooling System Outage — Schneider Electric
  12. Uptime Institute Global Data Center Survey 2025 — average annual PUE 1.54 — Uptime Institute, 2025
  13. U.S. EPA — Greenhouse Gas Emissions from a Typical Passenger Vehicle: 10,180 g CO₂ per gallon of diesel (≈2.69 kg/L) — U.S. EPA

Waɗanda ke yin wannan a matsayin sana'a

Samfurin ilimi — ba don yanke shawarar aiki ba. Wuraren gaske suna daidaita kowace ƙayyadaddiyar ƙima da kayan aiki da bayanansu.